Trading & Supply · Fabrication & Installation · Dubai, UAE
Glass Products · 05

Fire Rated Glass


Fire-resisting glazing supplied as part of an approved system, for screens, doors and protected escape routes.

Fire rated glazing is engineered to hold back flame, smoke and – in some classifications – radiant heat, for a defined period. It is a system product: the glass, the frame, the seals and the installation are certified together, and substituting any one element invalidates the rating.

The system is what is certified, not the glass

Fire-resisting glazing is tested and classified as a complete assembly – glass, frame, beads, seals, fixings and the way it is installed. A pane on its own carries no classification.

This is the single most common misunderstanding on fire glazing, and it has a practical consequence: substituting the frame, the seal or the fixing method for something not in the tested assembly invalidates the classification, even if the glass is unchanged. We supply against the approved specification and pass on the manufacturer's documentation for what we deliver.

What the selection depends on

Integrity or integrity plus insulation

Integrity-only glazing holds back flame and smoke. Insulating glazing also limits heat transmission to the protected side, which is what allows a longer safe dwell time in an escape route. Which is required comes from the fire strategy, not from the glass.

The required period

Set by the fire strategy for that compartment or route. We do not select it.

Frame compatibility

The frame is part of the tested assembly. A glass type and a frame that were never tested together cannot be combined and still claim the classification.

Documentation

Test certificates for the supplied system will be asked for at handover, and quite possibly again later during an insurance review or a sale.

What we need to quote

  • The classification and period required by the fire strategy
  • Pane sizes and quantities
  • Frame system, if already specified or existing
  • Location: screen, door leaf, over-panel or escape route
  • Whether the consultant has an approved system on the project

What commonly goes wrong

A specification that names a period but not whether insulation is required. The two are materially different in cost and build-up, and the gap is usually found at submittal rather than at enquiry.

The other is mixing components from different tested assemblies to save money or time. It will not pass approval, and it should not.

Specification noteFire rated glazing must be selected and installed as a complete certified system in line with the project's approved fire strategy and the requirements of the relevant UAE civil defence authority. We supply against the approved specification and provide the manufacturer's documentation.
Fire rated glazing installed to a fireplace enclosure
Related

More from Glass Products


01 Stacked panes of clear float glass showing polished edges

Clear Float Glass

The standard flat glass most other architectural glass is processed from.

View details
Clear Float Glass
02 Ultra clear low-iron glass panes with minimal green edge tint

Ultra Clear Glass

Low-iron glass with the green edge cast removed, for thick or layered applications.

View details
Ultra Clear Glass
03 Edge detail of laminated safety glass showing the bonded interlayer

Laminated Glass

Bonded panes that hold their fragments on breakage – the standard for balustrades and overhead.

View details
Laminated Glass
04 Tinted glass samples in bronze, grey, green, blue and neutral shades

Tinted Glass

Colour through the body of the glass, cutting glare and solar gain on exposed elevations.

View details
Tinted Glass

Need fire rated glass priced?

Tell us the project and the programme. We will confirm whether it is stock or made to order, and price it accordingly.

WhatsApp